Yuchai 600 kW open-frame diesel generator

- Power
- 600 kW
- 700 kVA, maximum 620 kW
- Consumption at 100%
- 120 L/h
- at 50%: 60.7 L/h
- Warranty
- 2 years
- or 1,500 engine hours
Specifications
Generator set
- Rated power
- 600 kW / 700 kVA
- Maximum power
- 620 kW / 725 kVA
- Voltage
- 400 / 230 V
- Frequency
- 50 Hz
- Power factor
- 0.8
Engine
| Option 1 | Option 2 | |
|---|---|---|
| Model | YC6TD840-D31 | YC6TD1000 |
| Type | 4-cylinder inline / 4-stroke | inline, 4-stroke, turbocharged |
| Number of cylinders | 6 | 6 |
| Displacement | 19.5 L | 19.6 L |
| Bore and stroke | 152×180 mm | 152×180 mm |
| Cooling system | liquid | liquid |
| Coolant capacity | 60 L | – |
| Oil capacity | 52 L | 55 L |
| Fuel consumption | ≤195 g/kWh | ≤195 g/kWh |
| Speed governor | mechanical | electronic |
| Rotation speed | 1500 rpm | 1500 rpm |
| Consumption at 50 / 75 / 100% load | 60.7 / 90.1 / 120 L/h | 83.3 / 121.1 / 164.4 L/h |
The engine is supplied based on warehouse availability; the generator power stays the same.
Alternator
- Type
- brushless
- Winding
- copper
- Power
- 620 kW
- Voltage
- 400 / 230 V
- Frequency
- 50 Hz
- Current
- 920 A
- Number of phases
- three-phase, four-wire
- Voltage stabilizer
- ATS
- Insulation class
- H
- Protection class
- IP23
- Voltage regulator
- 0.5
Dimensions
- Length × Width × Height
- 4800 × 2200 × 2500 mm
Fuel consumption
- 50 %60.7 L/h
- 75 %90.1 L/h
- 100 %120 L/h
At 50, 75 and 100% of rated power.
Questions about Yuchai 600 kW
How many kVA is the Yuchai 600 kW open-frame generator?
Rated (prime) power is 600 kW, which is 700 kVA. Maximum power is 620 kW; the generator can run at it only for short periods, so size by rated power with a margin.
How much fuel does it use?
At 50% load: 60.7 L/h, at 75%: 90.1 L/h, at full load: 120 L/h.
Is there a fuel tank?
For an open-frame generator, the tank is available at extra cost. We will size it for the required autonomous run time.
Does it have an ATS?
The ATS is available at extra cost. It starts the generator automatically on mains failure and switches the load back when mains power returns.
What cable is needed for connection?
Rated current 1,083 A. Copper cable: 4 runs of 3×150 + 1×70 mm² from the generator to the panel, laid in air or on trays. For long runs, our manager will recalculate the cross-section.
What are the dimensions and weight?
Length × Width × Height: 4800 × 2200 × 2500 mm.
What is the warranty?
2 years or 1,500 engine hours, whichever comes first.
How much does it cost?
Price is quoted on request: it depends on configuration and delivery time. Add the model to your quote cart or message us on WhatsApp, and we will send a quotation.